Reverse Phase Relay

2532

The Model 2532 Reverse Phase Relay provides essential protection against phase reversal in industrial applications. Its sensing mechanism detects phase sequence on both Wye and Delta systems, preventing potential equipment damage. Operating across a wide 190 to 500 VAC range, this relay ensures compatibility with diverse power systems. A rapid 0.05-second response time minimizes exposure to incorrect phase conditions, safeguarding connected machinery. The robust machine tool case, constructed from ABS plastic, contributes to its durability in demanding environments. With SPDT 10A output contacts and an electrical life of 100,000 operations at rated load, the unit offers consistent performance. Furthermore, its -20° to +131° F operating temperature range and 0-97% humidity tolerance without condensation ensure reliable function in varied climates. Backed by a 5-year unconditional warranty, the Model 2532 offers dependable phase protection.

Reverse Phase Relay

DOWNLOADS:

2532

Specifications

Sensing TypePhase reversal on Wye or Delta
Voltage Range190 to 500 VAC
Case TypeMachine tool case
Nominal Voltage190-500 VAC (phase to phase)
Frequency50 to 60Hz
Power Consumption2W per phase
Transient Protection2500 VRMS for 10ms
Repeat Accuracy± 0.1% (fixed conditions)
Response Time.05 seconds
Reset Time.05 seconds
Reset TypeAutomatic
Dead BandApproximately 2%
Output ContactsSPDT 10A at 240VAC resistive
Contact Rating15 amps up to 150 vac
Contact Rating10 amps up to 240 vac
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Case MaterialABS plastic
MountingSurface
Agency ApprovalUL Recognized and CSA Certified
IndicatorLED will illuminate with correct ABC phase rotation
Warranty5-year Unconditional Warranty

FAQs

What voltage ranges does the Model 2532 Reverse Phase Relay support?
The Model 2532 supports a nominal voltage range of 190 to 500 VAC (phase to phase) for phase reversal sensing.
What is the response time for phase reversal detection with this relay?
The Model 2532 Reverse Phase Relay has a response time of 0.05 seconds for detecting phase reversal conditions.
What are the operating environmental limits for the Model 2532?
This relay operates reliably within a temperature range of -20° to +131° F and tolerates 0-97% humidity without condensation.