2500-415

2500-415

The Model 2500 3-Phase Monitor provides essential protection for industrial systems. This device continuously monitors for critical conditions including phase loss, phase reversal, low voltage, and voltage unbalance. Its automatic reset feature ensures seamless operation following a fault correction, minimizing downtime. Equipped with heavy-duty output contacts, the Model 2500 offers robust control capabilities. The unit is UL Listed to U.S. and Canadian safety standards, affirming its reliability in demanding environments. With an adjustable trip delay from 1 to 10 seconds and a repeat accuracy of ±1% of full scale, it delivers precise and consistent performance. Available in multiple nominal AC voltage configurations, including 120V to 600V, it adapts to diverse applications. Its humidity tolerance of 0-97% without condensation further enhances its utility in varied industrial settings. This monitor is a dependable component for maintaining system integrity.

The Model 2500 3-Phase Monitor is designed to continuously monitor
3-phase power lines for abnormal conditions. This device features
solid-state voltage and phase-angle sensing circuits, which drive a SPDT
electromechanical output relay. When the correct voltage and phase
sequence is applied to a specified Model 2500, the output relay will not
energize. An under voltage, phase reversal, phase unbalance or phase
loss condition will cause the output relay to energize, even if
regenerated voltage is present. Complete power loss will not cause Model
2500 to trip. The 2501 version of this unit operates in fail-safe mode,
and the contacts de-energize on a fault condition. A neutral connection
is not required, allowing the Model 2500 or 2501 to be used with either
Wye or Delta system configurations. Each option on the Model 2500 or
2501 monitor is adjustable throughout its operating range. The
adjustment pots and LED indicators for VOLTAGE ADJUST, UNBALANCE ADJUST
and TIME DELAY are mounted on the front of the unit for easy access.
Seven versions of the Model 2500 or 2501 cover voltage ranges from 120
to 600 VAC, and are UL Listed and CSA Certified.

Specifications

Monitored ConditionsPhase Loss or Reversal, Low Voltage or Voltage Unbalance
Reset TypeAutomatic
Output Contacts FeatureHeavy Duty
Agency ApprovalUL Listed to U.S. and Canadian Safety Standards
Relay OperationWhen the correct voltage and phase sequence is applied, the output relay will not energize. An under voltage, phase reversal, phase unbalance or phase loss condition will cause the output relay to energize. Complete power loss will not cause a trip.
Config: Model Versions2500-120, 2500-208, 2500-240, 2500-380, 2500-415, 2500-480, 2500-600
Config: Nominal AC Voltage120, 208, 240, 380, 415, 480, 600
Config: Adjustment Range84-114V, 146-198V, 168-229V, 266-361V, 290-394V, 336-456V, 420-570V
Frequency50/60Hz
Unbalance Adjustment Range2 to 10% per NEMA specifications
Trip Delay Adjustment Range1 to 10 seconds (1 sec increments)
Power Consumption4.5W per phase
Repeat Accuracy±1% of full scale
Reset Time150ms nominal
Dead Band2% of full scale
Output ContactsSPDT 30 amps at 28VDC/300VAC 50/60Hz
Output Contacts (High Voltage)5 amps at 480/600VAC 50/60Hz 0.75 PF
Operating Temperature-4° to +131° F
Humidity Tolerance0-97% without condensation
Enclosure MaterialABS plastic
MountingSurface
Warranty5-year Unconditional Warranty

FAQs

What conditions does the Model 2500 3-Phase Monitor detect?
The Model 2500 detects phase loss or reversal, low voltage, and voltage unbalance conditions.
What are the specifications for the output contacts on the Model 2500?
The Model 2500 features SPDT output contacts rated for 30 amps at 28VDC/300VAC and 5 amps at 480/600VAC.
What is the operating temperature and humidity range for the Model 2500?
The Model 2500 operates from -4° to +131° F and tolerates 0-97% humidity without condensation.