Model 21M 3-Phase Monitor (Manual Reset, 190-480 VAC)

21M

The Model 21M 3-Phase Monitor provides essential protection for industrial systems. Operating across a 190-480 VAC range, this device detects critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance. Its manual reset functionality ensures controlled system restarts after a fault, preventing automatic re-energization until inspected. Users can adjust trip delay times for over, under, and unbalance conditions from 1-30 seconds, allowing for application-specific tuning to minimize nuisance trips. The unit also features a restart delay adjustable from 1-500 seconds. With a compact design (2.98" L x 1.77" W x 2.45" H) and a 5-year unconditional warranty, the Model 21M offers reliable performance and system integrity. It is compatible with both Wye and Delta systems, requiring no neutral connection, simplifying installation.

Universal 3Ph Monitor

DOWNLOADS:

21m

Specifications

Model TypeManual Reset
Operating Voltage190-480 VAC
Power Consumption3.7W at 480V
Auto RangesYes
Monitored ConditionsPhase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay Time (Over, Under, & Unbalanced)1-30 sec., adjustable
Trip Delay Time (Single-Phasing Faults Unbalance > 15%)1 sec., fixed
Trip Delay Time (Reverse Phase)1 sec., fixed
Restart Delay1-500 sec., adjustable
Manual Reset Input5V open circuit/500µA short circuit
Output ContactsSPDT 10A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialNoryl plastic
Mounting8-Pin Socket (**sold separately)
Recommended Socket51x120
Additional Options/SG = Silver with Gold Flash Contacts
Agency ApprovalUL Recognized (U.S. and Canada) (For use in a Pollution Degree 2 Environment)
Neutral ConnectionNot required
System CompatibilityWye or Delta systems
Recommended Fuse1A 600VAC
Warranty5-year Unconditional Warranty

FAQs

What operating voltage range does the Model 21M 3-Phase Monitor support?
The Model 21M supports an operating voltage range of 190-480 VAC.
What types of electrical faults does the Model 21M monitor for?
It monitors for phase loss, phase reversal, over/under voltage, and voltage unbalance conditions.
Are the trip delay times adjustable on the Model 21M?
Yes, the trip delay time for over, under, and unbalance conditions is adjustable from 1-30 seconds.