Model 21-H 3-Phase Monitor (Auto Reset, 475-600 VAC)
The Model 21-H 3-Phase Monitor ensures operational continuity in industrial environments. This auto-reset device provides comprehensive protection for 475-600 VAC systems. It actively monitors for critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance, safeguarding connected equipment. Adjustable trip delay times, ranging from 1 to 30 seconds, allow for precise system-specific response tuning, preventing nuisance trips while ensuring timely intervention. A configurable restart delay, from 1 to 500 seconds, further enhances system stability and controlled recovery after fault conditions. Its robust SPDT 10A output contacts at 240VAC resistive integrate seamlessly into diverse control circuits. The unit's compact design and UL recognition confirm its suitability for demanding applications, contributing to reliable power system management and reduced downtime.
Universal 3Ph Monitor
Specifications
| Model Type | Auto Reset |
|---|---|
| Operating Voltage | 475-600 VAC |
| Power Consumption | 4.5W at 600V |
| Auto Ranges | No |
| Monitored Conditions | Phase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance |
| Frequency | 50/60Hz |
| Type of Measurement | RMS |
| Under Voltage Trip | 90% ±1% (% of setpoint) |
| Under Voltage Reset | 93% ±1% (% of setpoint) |
| Over Voltage Trip | 110% ±1% (% of setpoint) |
| Over Voltage Reset | 107% ±1% (% of setpoint) |
| Voltage Unbalance Trip | 2-8%, adjustable (conforms to NEMA) |
| Voltage Unbalance Reset | Trip setting minus 0.7% |
| Trip Delay Time (Over, Under, & Unbalanced) | 1-30 sec., adjustable |
| Trip Delay Time (Single-Phasing Faults Unbalance > 15%) | 1 sec., fixed |
| Trip Delay Time (Reverse Phase) | 1 sec., fixed |
| Restart Delay | 1-500 sec., adjustable |
| Manual Reset Input | 5V open circuit/500µA short circuit |
| Output Contacts | SPDT 10A at 240VAC resistive |
| Operating Temperature | -20° to +140° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | Noryl plastic |
| Mounting | 8-Pin Socket (**sold separately) |
| Recommended Socket | 51x120 |
| Additional Options | /SG = Silver with Gold Flash Contacts |
| Agency Approval | UL Recognized (U.S. and Canada) (For use in a Pollution Degree 2 Environment) |
| Neutral Connection | Not required |
| System Compatibility | Wye or Delta systems |
| Recommended Fuse | 1A 600VAC |
| Warranty | 5-year Unconditional Warranty |