20AB-M

20AB-M

The 20AB-M 3-Phase Monitor offers essential protection for industrial electrical systems. This device precisely monitors critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance. Its adjustable trip delay, ranging from 1 to 30 seconds, allows for tailored response times to system anomalies. The unit's manual reset capability ensures controlled system restarts following a fault condition. Operating across a wide 190-480 VAC range, the 20AB-M integrates seamlessly into diverse applications. Its robust design and comprehensive monitoring capabilities contribute to enhanced operational reliability and equipment longevity. This monitor provides a dependable solution for maintaining system integrity.

The Model 20AB is a microcontroller-based universal 3-phase monitor for
protecting 3-phase motors from abnormal power conditions. It can detect
under voltage, over voltage, voltage unbalance, reverse phase, and
single-phasing even when regenerated voltage is present. The Model 20AB
includes adjustable trip and restart delays to prevent nuisance tripping
during power fluctuations and short cycling in compressor applications.
The LED status indicators and adjustment pots for Voltage Adjustment, %
Unbalance, Restart Delay and Trip Delay are mounted on the front of the
unit for easy access. The 20AB has 1 normally open (N.O.) & 1
normally closed (N.C.) isolated contacts.Automatic or manual restart
versions are available. The Model 20AB does not require a neutral
connection and can be used on either Wye or Delta systems. All versions
of the Model 20AB are UL Recognized (U.S. and Canada) and are available
with optional gold flashed silver contacts for low current applications.

Specifications

Reset TypeManual Reset
Operating Voltage190-480 VAC
Power Consumption3.7W at 480V
Auto RangesYes
Monitored ConditionsPhase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay Time (Over, Under, & Unbalanced)1-30 sec., adjustable
Trip Delay Time (Single-Phasing Faults)1 sec., fixed
Trip Delay Time (Unbalance > 15%)1 sec., fixed
Restart DelayDisabled in manual reset mode
Manual Reset Input5V open circuit/500µA short circuit
Manual Reset RequirementExternal N.O. momentary pushbutton required for manual reset
Output Contacts1x N.C., 1x N.O. 7.5A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Terminal Torque3.5 in. lbs. maximum
Wire TypeStranded or solid 14-26 AWG, 1/terminal
Enclosure MaterialNoryl plastic
MountingDIN Rail or Surface Mount
Additional Options/SG = Silver with Gold Flash Contacts
Warranty5-year Unconditional Warranty

FAQs

What is the operating voltage range for the 20AB-M monitor?
The 20AB-M 3-Phase Monitor operates within a 190-480 VAC range.
Which conditions does the 20AB-M monitor?
The 20AB-M monitors phase loss, phase reversal, over/under voltage, and voltage unbalance.
What are the output contact specifications for this device?
The device features 1x N.C. and 1x N.O. output contacts, rated at 7.5A at 240VAC resistive.