20AB-LM

20AB-LM

The Model 20AB 3-Phase Monitor, SKU 20AB-LM, provides essential protection for industrial three-phase systems. This device monitors critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance. Its adjustable trip delay times, ranging from 1 to 30 seconds, allow for precise system integration and fault response customization. Operating at 95-120 VAC, the unit ensures consistent performance across various applications. The manual reset feature offers controlled system re-engagement after a fault, preventing unintended restarts. With output contacts rated at 7.5A at 240VAC resistive, it facilitates reliable control circuit integration. This monitor is designed for sustained operation within a -20° to +140° F temperature range, accommodating diverse industrial environments. Its robust Noryl plastic enclosure and DIN rail or surface mount options enhance installation flexibility and durability.

The Model 20AB is a microcontroller-based universal 3-phase monitor for
protecting 3-phase motors from abnormal power conditions. It can detect
under voltage, over voltage, voltage unbalance, reverse phase, and
single-phasing even when regenerated voltage is present. The Model 20AB
includes adjustable trip and restart delays to prevent nuisance tripping
during power fluctuations and short cycling in compressor applications.
The LED status indicators and adjustment pots for Voltage Adjustment, %
Unbalance, Restart Delay and Trip Delay are mounted on the front of the
unit for easy access. The 20AB has 1 normally open (N.O.) & 1
normally closed (N.C.) isolated contacts.Automatic or manual restart
versions are available. The Model 20AB does not require a neutral
connection and can be used on either Wye or Delta systems. All versions
of the Model 20AB are UL Recognized (U.S. and Canada) and are available
with optional gold flashed silver contacts for low current applications.

Specifications

Reset TypeManual Reset
Operating Voltage95-120 VAC
Power Consumption3.7W at 120V
Auto RangesNo
Monitored ConditionsPhase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay Time (Over, Under, & Unbalanced)1-30 sec., adjustable
Trip Delay Time (Single-Phasing Faults)1 sec., fixed
Trip Delay Time (Unbalance > 15%)1 sec., fixed
Restart DelayDisabled in manual reset mode
Manual Reset Input5V open circuit/500µA short circuit
Manual Reset RequirementExternal N.O. momentary pushbutton required for manual reset
Output Contacts1x N.C., 1x N.O. 7.5A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Terminal Torque3.5 in. lbs. maximum
Wire TypeStranded or solid 14-26 AWG, 1/terminal
Enclosure MaterialNoryl plastic
MountingDIN Rail or Surface Mount
Additional Options/SG = Silver with Gold Flash Contacts
Warranty5-year Unconditional Warranty

FAQs

What conditions does the 20AB-LM 3-Phase Monitor detect?
The 20AB-LM monitors for phase loss, phase reversal, over/under voltage, and voltage unbalance, operating within a 95-120 VAC range at 50/60Hz.
How are trip delays and system resets managed on the 20AB-LM?
The 20AB-LM features adjustable trip delays from 1-30 seconds for various faults. It utilizes a manual reset type, requiring an external momentary pushbutton. Restart delay is disabled in this mode.
What are the output contact specifications and environmental operating limits for the 20AB-LM?
The 20AB-LM provides 1x N.C. and 1x N.O. output contacts, rated at 7.5A at 240VAC resistive. It operates reliably from -20° to +140° F with 0-97% humidity without condensation.
Select your currency
CAD Canadian dollar