3-Phase Monitor with Adjustable Trip & Restart Delays

20AB

The Model 20AB 3-Phase Monitor provides essential protection for industrial systems. This device monitors critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance, ensuring operational integrity. Its adjustable trip delay, ranging from 1 to 30 seconds, allows for precise response timing to transient events, preventing unnecessary shutdowns. Furthermore, the adjustable restart delay, configurable from 1 to 500 seconds, facilitates controlled system re-engagement, safeguarding connected equipment. Operating across a 190-480 VAC range with auto-ranging capabilities, it offers versatility for various applications. The unit's auto-reset functionality minimizes manual intervention, contributing to continuous system uptime. With output contacts rated 7.5A at 240VAC resistive, it integrates seamlessly into control circuits. This monitor is designed for reliable performance in demanding industrial environments, offering comprehensive phase protection.

Unv 3Ph Monitor

DOWNLOADS:

20ab

Specifications

Reset TypeAuto Reset
Operating Voltage190-480 VAC
Power Consumption3.7W at 480V
Auto RangesYes
Monitored ConditionsPhase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay Time (Over, Under, & Unbalanced)1-30 sec., adjustable
Trip Delay Time (Single-Phasing Faults)1 sec., fixed
Trip Delay Time (Unbalance > 15%)1 sec., fixed
Restart Delay1-500 sec., adjustable
Manual Reset Input5V open circuit/500µA short circuit
Output Contacts1x N.C., 1x N.O. 7.5A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Terminal Torque3.5 in. lbs. maximum
Wire TypeStranded or solid 14-26 AWG, 1/terminal
Enclosure MaterialNoryl plastic
MountingDIN Rail or Surface Mount
Additional Options/SG = Silver with Gold Flash Contacts
Warranty5-year Unconditional Warranty

FAQs

What conditions does the 20AB 3-Phase Monitor detect?
The 20AB monitors phase loss, phase reversal, over/under voltage, and voltage unbalance.
What are the adjustable delay ranges for the 20AB monitor?
The trip delay for over, under, and unbalanced conditions is adjustable from 1 to 30 seconds. The restart delay is adjustable from 1 to 500 seconds.
What are the operating voltage and output contact specifications for the 20AB?
The operating voltage range is 190-480 VAC. It features 1x N.C. and 1x N.O. output contacts, rated 7.5A at 240VAC resistive.