20AA-M
The MODEL 20AA-M 3-Phase Monitor provides essential protection for industrial systems. This unit monitors critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance across a broad 190-480 VAC operating range. Its adjustable trip delay, configurable from 1 to 30 seconds, allows for precise response to transient faults, preventing unnecessary shutdowns. Furthermore, the adjustable restart delay, ranging from 1 to 500 seconds, facilitates controlled system re-engagement after a fault condition has cleared. The manual reset functionality, requiring an external momentary pushbutton, ensures operator intervention for safety and system integrity. With dual 7.5A at 240VAC resistive output contacts and a durable Noryl plastic enclosure, the 20AA-M offers reliable performance and integration flexibility. This monitor is designed for critical applications demanding consistent power quality oversight and robust equipment protection.
The Model 20AA is a microcontroller-based universal 3-phase monitor for
protecting 3-phase motors from abnormal power conditions. It can detect
under voltage, over voltage, voltage unbalance, reverse phase, and
single-phasing even when regenerated voltage is present. The Model 20AA
includes adjustable trip and restart delays to prevent nuisance tripping
during power fluctuations and short cycling in compressor applications.
The LED status indicators and adjustment pots for Voltage Adjustment, %
Unbalance, Restart Delay and Trip Delay are mounted on the front of the
unit for easy access. The 20AA has 2 normally open (N.O.) isolated
contacts.Automatic or manual restart versions are available. The Model
20AA does not require a neutral connection and can be used on either Wye
or Delta systems. All versions of the Model 20AA are UL Recognized
(U.S. and Canada) and are available with optional gold flashed silver
contacts for low current applications.
Out of stock
$272.00
Specifications
| Model Type | Manual Reset |
|---|---|
| Manual Reset Requirement | External N.O. momentary pushbutton required for manual reset. |
| Monitored Conditions | Phase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance |
| Indicators | LED Status Indicators |
| Operating Voltage | 190-480 VAC |
| Power Consumption | 3.7W at 480V |
| Auto Ranges | Yes |
| Frequency | 50/60Hz |
| Type of Measurement | RMS |
| Under Voltage Trip | 90% ±1% (% of setpoint) |
| Under Voltage Reset | 93% ±1% (% of setpoint) |
| Over Voltage Trip | 110% ±1% (% of setpoint) |
| Over Voltage Reset | 107% ±1% (% of setpoint) |
| Voltage Unbalance Trip | 2-8%, adjustable |
| Voltage Unbalance Conformance | NEMA |
| Voltage Unbalance Reset | Trip setting minus 0.7% |
| Trip Delay Time (Over, Under, & Unbalanced) | 1-30 sec., adjustable |
| Trip Delay Time (Single-Phasing Faults) | 1 sec., fixed |
| Trip Delay Time (Unbalance > 15%) | 1 sec., fixed |
| Restart Delay | 1-500 sec., adjustable |
| Manual Reset Input | 5V open circuit/500µA short circuit |
| Output Contacts | 2x N.O. (Isolated) |
| Output Contact Rating | 7.5A at 240VAC resistive |
| Operating Temperature | -20° to +140° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Terminal Torque | 3.5 in. lbs. maximum |
| Wire Type | Stranded or solid 14-26 AWG, 1/terminal |
| Enclosure Material | Noryl plastic |
| Mounting | DIN Rail or Surface Mount |
| Dimension Tolerance | ±0.06 |
| Optional Feature | /SG = Silver with Gold Flash Contacts |
| Warranty | 5-year Unconditional Warranty |