19-208/240-400

19-208/240-400

The Model 19 3-Phase Monitor offers essential protection for industrial systems. This device detects critical anomalies including phase loss, low voltage, and phase reversal, ensuring operational integrity. Its adjustable trip and restart delays, ranging from 1-30 seconds and 1-300 seconds respectively, allow for precise system integration and controlled recovery. The automatic reset feature minimizes downtime. Compatible with both Wye and Delta systems, it does not require a neutral connection, simplifying installation. With a five-year unconditional warranty, this monitor provides reliable performance and long-term value, safeguarding equipment against electrical irregularities. Its robust design ensures consistent operation in demanding environments, tolerating 0-97% humidity without condensation and operating from -20° to +131° F. Power consumption is a low 2.4W.

The Model 19 continuously monitors 3-phase power lines for abnormal
conditions. When properly adjusted, the Model 19 monitor will detect
phase loss on a loaded motor even when regenerated voltage is present.
This device consists of a microcontroller with a voltage and phase-angle
sensing circuit, driving an electromechanical relay. When correct
voltage and phase rotation are applied, the internal relay will
energize. A fault condition will de-energize the relay. When the fault
is corrected, the monitor will automatically reset. An adjustable
restart delay prevents short cycling in compressor applications and an
adjustable trip delay prevents nuisance tripping during power
fluctuations. The Model 19 does not require a neutral connection and
can be used with Wye or Delta systems. Voltage ranges are sufficiently
wide to allow for proper adjustment to existing conditions. Both FAULT
and NORM condition indicators are provided to aid in adjustment and
system trouble-shooting. The Model 18 is UL Recognized in the U.S. and
Canada and is available with optional gold flashed silver contacts for
low current applications.

Specifications

DetectionPhase loss, low voltage, phase reversal
Reset TypeAutomatic
WarrantyFive year unconditional
Nominal AC (phase to phase)208/240VAC
Adjustment range160-240VAC
Frequency400Hz
Power consumption2.4W
Transient protection2500VAC for 10ms
Repeat accuracy± 0.1% of set point (fixed conditions)
Trip delay1-30 sec.
Restart Delay1-300 sec.
Dead bandApproximately 2%
Output contactsSPDT 10 amps at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temp-20° to +131° F
Humidity tolerance0-97% w/o condensation
Enclosure materialNORYL plastic cover; 6/6 Nylon base
Mounting8-pin socket (**sold separately)
Accessory SocketOrder 8-pin socket number 51X120
System CompatibilityWye or Delta systems
Neutral ConnectionNot required
IndicatorsFAULT and NORM condition indicators

FAQs

What types of electrical conditions does the Model 19 monitor detect?
The Model 19 detects phase loss, low voltage, and phase reversal conditions within a system.
What are the adjustable delay ranges for trip and restart functions on this monitor?
The trip delay is adjustable from 1 to 30 seconds, and the restart delay is adjustable from 1 to 300 seconds.
Is a neutral connection required for the operation of the Model 19 3-Phase Monitor?
No, a neutral connection is not required for the operation of the Model 19 3-Phase Monitor. It is compatible with Wye or Delta systems.