AC Current Monitor

1732

The Model 1732 AC Current Monitor provides essential current sensing capabilities for industrial systems. This self-powered unit eliminates the need for an external supply voltage, simplifying installation and reducing wiring complexity. It accurately monitors AC currents within a 25 to 150 amp range, offering both over and under current detection. With a rapid 100ms response time, it ensures timely system protection and control. The device features a SPDT 10A at 240VAC resistive contact rating and maintains 1% maximum repeat accuracy across a -20° to +140° F operating temperature range. Dual LED indicators provide clear status feedback, aiding in quick diagnostics. Mounting options include surface or 35mm DIN rail, enhancing application versatility. Its screwdriver adjustable settings allow for precise calibration. This monitor delivers consistent performance for critical operational oversight.

Current Monitor Dr

DOWNLOADS:

1732

Specifications

Supply Voltagenone required
Input Current Minimum25 amps
Input Current Maximum150 amps
Adjustment Range25 to 150 amps
Maximum Wire Size2 AWG
Response Time100ms
Contact RatingSPDT 10A at 240VAC resistive
Repeat Accuracy1%
Dead BandApproximately 2%
Operating Temperature-20° to +140° F
ResetAutomatic
Terminals1/4" quick connects
Enclosure MaterialABS plastic
MountingSurface Mount or DIN Rail 35mm
Current SensingOver or Under Current
IndicatorsDual LED Condition Indicators
Energize CurrentA current greater than 25 amps is needed to energize the internal relay
AC Current Frequency Range50 to 400Hz
Adjustment MethodScrewdriver adjustable
Warranty1 year

FAQs

What is the operational current sensing range for the Model 1732 AC Current Monitor?
The Model 1732 monitors AC currents from 25 to 150 amps, capable of detecting both over and under current conditions.
What are the installation requirements and mounting options for this current monitor?
The Model 1732 requires no external supply voltage. It can be installed via surface mount or on a 35mm DIN rail.
What are the key performance specifications regarding response time and accuracy?
The unit features a 100ms response time and maintains a repeat accuracy of 1% maximum.