Model 2644 3-Phase Monitor

B2644-208/240VAC

The Model 2644 3-Phase Monitor offers essential protection for industrial electrical systems. Operating at 208/240VAC, it features an adjustable voltage range of 160-240V and a configurable response time from 0.2 to 20 seconds. This device reliably detects critical conditions such as phase loss, low voltage, and phase reversal, preventing equipment damage and operational downtime. Its DPDT 10 amp output contacts at 240VAC resistive ensure robust control. With a 5-year unconditional warranty and UL Recognized/CSA Certified approvals, the Model 2644 provides consistent performance and long-term reliability in demanding environments. Its auto-reset function simplifies maintenance, reducing intervention needs. The unit's transient protection of 2500 VRMS for 10ms enhances durability. Operating across a -20° to +131° F temperature range, it maintains functionality in varied conditions.

3-Ph Pwr Mon

DOWNLOADS:

b2644-208-240vac

Specifications

Reset TypeAuto Reset
Nominal AC Voltage208/240VAC (phase to phase)
Adjustment Range160-240V
Frequency60Hz
Power Consumption1.5W
FunctionDetects Phase Loss, Low Voltage and Phase Reversal
Warranty5 Year Unconditional Warranty
Transient Protection2500 VRMS for 10ms
Repeat Accuracy± 0.1% of setpoint (fixed conditions)
Response TimeAdjustable 0.2 to 20 seconds ±10%
Dead BandApproximately 2%
Output ContactsDPDT 10 amps at 240VAC resistive
Expected Relay Life, Mechanical10 million operations
Expected Relay Life, Electrical100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
MountingSurface
Agency ApprovalsUL Recognized and CSA Certified

FAQs

What is the nominal operating voltage and adjustment range for the Model 2644?
The Model 2644 operates with a nominal AC voltage of 208/240VAC (phase to phase) and has an adjustment range of 160-240V.
What types of electrical faults does the Model 2644 monitor detect?
This monitor detects phase loss, low voltage, and phase reversal, providing comprehensive protection for 3-phase systems.
What are the specifications for the output contacts on the Model 2644?
The Model 2644 features DPDT 10 amp output contacts at 240VAC resistive, designed for reliable switching.