Submersible Pump Controller

422

The MODEL 422 Submersible Pump Controller provides essential motor protection by monitoring true motor power. This device detects both overload and underload conditions, preventing potential equipment damage and operational downtime. Its compatibility with single-phase or 3-phase systems and a wide input voltage range (100-130VAC or 200-250VAC) offers installation flexibility. Configurable trip and restart delays, ranging from 0.3 to 180 seconds and 0.1 to 4 hours respectively, allow for precise system integration. With a robust design and a mechanical relay life of 10 million operations, the controller ensures sustained performance in demanding industrial environments. The unit's 1% repeat accuracy under fixed conditions supports consistent operational parameters. Furthermore, transient protection up to 2500V for 10ms enhances its resilience. An output of 4-20mA is available for chart recorders, facilitating data logging. This contributes to system reliability and longevity, minimizing maintenance requirements.

Submrs Pump Control Csa

DOWNLOADS:

422

Specifications

Monitored ParameterTrue Motor Power (volts x current x power factor)
DetectionMotor Overload or Underload
Phase CompatibilitySingle-phase or 3-phase
Input Voltage Range100-130VAC or 200-250VAC
Frequency50/60Hz
Power Consumption0.5 VA
Nominal Current2.5 amps
Minimum Current0.25 amps
Current Adjustment0-5 amps x PF
Current Output4-20mA for chart recorders
Repeat Accuracy1% (fixed conditions)
OutputSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Trip DelayOFF or 0.3 to 180 seconds
Restart DelayOFF or 0.1 to 4 hours
Indicator (Red LED)Overload or Underload; tripped
Indicator (Yellow LED)Restart timing
Transient Protection2500V for 10ms
Operating Temperature-20° to 131° F
Humidity Tolerance97% w/o condensation
Enclosure MaterialABS plastic
Agency ApprovalsUL Listed to US and Canadian safety standards CSA Certified
Config: Overload Restart (DIP SW 1)ON: Disabled, OFF: Enabled
Config: Restart Delay (DIP SW 2)ON: Enabled, OFF: Disabled
Config: Reset Button (DIP SW 3)ON: Enabled, OFF: Disabled
Config: Trip Delay (DIP SW 4)ON: Enabled, OFF: Disabled

FAQs

What motor conditions does the MODEL 422 controller monitor?
The MODEL 422 monitors true motor power to detect both overload and underload conditions.
What voltage and phase configurations are compatible with the MODEL 422?
The controller is compatible with single-phase or 3-phase systems, accepting input voltages of 100-130VAC or 200-250VAC at 50/60Hz.
What are the configurable delay options for the MODEL 422?
The MODEL 422 offers a trip delay from 0.3 to 180 seconds and a restart delay from 0.1 to 4 hours, both configurable via DIP switches.