Model 362 Interval Timer

362-H-1MIN

The Model 362 Interval Timer provides precise timing control for industrial applications. Its digital configuration supports timing ranges from 0.1 seconds to 1023 minutes, accommodating diverse operational requirements. Configurable for 10-28V AC/DC or 40-260V AC/DC, it integrates into various power systems. With a repeatability of ± 0.1% and an operating temperature range of -20°F to +140°F, this timer maintains consistent performance in demanding environments. DPDT contacts rated at 10A at 240VAC resistive ensure robust switching capabilities. The unit features 775V, 80 Joules transient protection, enhancing its durability. Timing adjustments are made via dip switches for precise setup. UL Recognized and CSA Certified, the Model 362 is backed by a 5-year unconditional warranty, underscoring its long-term operational stability and reliability in critical processes.

Interval Tmr

DOWNLOADS:

362-h-1min

Specifications

Typedigital
Config: VoltageL = 10-28V AC/DC, H = 40-260V AC/DC
Config: Timing range.1SEC: 0.1- 102.3 Sec., 1SEC: 1- 1023 Sec., 1MIN: 1- 1023 Min.
Accuracy± 2%
Repeatability± 0.1%
Recycle time100ms
Operating temperature-20°F to +140°F
ContactsDPDT
Contact rating10A at 240VAC resistive
Transient protection775V, 80 Joules
Humidity tolerance0 - 97% w/o condensation
Enclosure materialNORYL Plastic
Mounting8-pin socket (not included)
Agency approvalUL Recognized and CSA Certified
Config: Additional Options/C = Custom (Voltage and/or Timing), /SG = Silver with Gold Flash Contacts
UL Input Voltage10-28V AC/DC OR 40-260V AC/DC
UL Input Power3 Watts Max
UL Output240V AC, 10A, Resistive; 120V AC, 4A, General Use; 240V AC, 2A, General Use; C300, Pilot Duty
UL Pilot Duty120V: Make 15A, Break 1.5A; 240V: Make 7.5A, Break 0.75A
Warranty5-year unconditional warranty
Reset MethodThe supply voltage must be removed to reset the timer.
Adjustment ProcedureSet delay time by adding values of selected dip switches.
LED Status (Green)Energized
LED Status (Red)De-energized
LED Status (Flashing)Relay is Timing

FAQs

What are the available voltage configurations for the Model 362 Interval Timer?
The Model 362 supports low voltage (10-28V AC/DC) and high voltage (40-260V AC/DC) configurations.
How is the timing range adjusted on the Model 362 Interval Timer?
Timing range is set by adding values of selected dip switches, offering precise control from 0.1 seconds to 1023 minutes.
What are the environmental operating limits for the Model 362 Interval Timer?
The Model 362 operates reliably within a temperature range of -20°F to +140°F and tolerates 0-97% humidity without condensation.