Model 332 Interval Timer

332-L-180SEC

The Model 332 Interval Timer provides precise control for industrial applications. Its configurable voltage options, including 10-28V AC/DC and 40-260V AC/DC, accommodate diverse system requirements. Users can select timing ranges up to 300 seconds, ensuring operational flexibility for various processes. With an accuracy of ±5% and repeatability of ±2%, consistent performance is maintained across its -20°F to +140°F operating temperature range. The unit features DPDT contacts rated for 10A at 240VAC resistive, supported by 775V, 80 Joules transient protection. Constructed with NORYL plastic, it offers durability in challenging environments. UL Recognized and CSA Certified, the Model 332 is backed by a 5-year warranty, underscoring its reliability for critical timing functions and reducing downtime.

Interval Tmr

DOWNLOADS:

332-l-180sec

Specifications

Typeknob adj.
Config: VoltageL = 10-28V AC/DC, H = 40-260V AC/DC
Config: Timing range10SEC: 1- 10 Sec., 60SEC: 1- 60 Sec., 180SEC: 1- 180 Sec., 300SEC: 1- 300 Sec.
Accuracy± 5%
Repeatability± 2%
Recycle time100ms
Operating temperature-20°F to +140°F
ContactsDPDT
Contact rating10A at 240VAC resistive
Transient protection775V, 80 Joules
Humidity tolerance0 - 97% w/o condensation
Enclosure materialNORYL Plastic
Mounting8-pin socket (not included)
Agency approvalUL Recognized and CSA Certified
Config: Additional Options/C = Custom (Voltage and/or Timing), /SG = Silver with Gold Flash Contacts
UL Input Voltage10-28V AC/DC OR 40-260V AC/DC
UL Input Power3 Watts Max
UL Output240V AC, 10A, Resistive; 120V AC, 4A, General Use; 240V AC, 2A, General Use; C300, Pilot Duty
UL Pilot Duty120V: Make 15A, Break 1.5A; 240V: Make 7.5A, Break 0.75A
Warranty5-year unconditional warranty
Reset MethodThe supply voltage must be removed to reset the timer.
LED Status (Green)Energized
LED Status (Red)De-energized
LED Status (Flashing)Relay is Timing

FAQs

What voltage configurations are available for the Model 332 Interval Timer?
The Model 332 offers configurable voltage options: 10-28V AC/DC for low voltage applications and 40-260V AC/DC for higher voltage systems.
What are the timing capabilities and precision of the Model 332 Interval Timer?
The Model 332 provides timing ranges up to 300 seconds, with an accuracy of ±5% and a repeatability of ±2%.
What environmental conditions can the Model 332 Interval Timer withstand, and what are its contact ratings?
It operates from -20°F to +140°F with 0-97% humidity tolerance without condensation. Contacts are DPDT, rated at 10A at 240VAC resistive.