3-Phase Monitor with Adjustable Trip & Restart Delays

22LM

The 22-LM 3-Phase Monitor provides essential protection for industrial systems, ensuring operational continuity and equipment longevity. Its adjustable trip delay, ranging from 1 to 30 seconds for voltage and unbalance faults, allows for precise system response customization, preventing unnecessary shutdowns while safeguarding machinery. A configurable restart delay, from 1 to 500 seconds, further enhances operational control by managing system re-engagement after a fault condition, reducing potential stress on motors and other components. This unit features a manual reset, ensuring deliberate system re-engagement only when conditions are verified safe. With an operating voltage of 95-120 VAC and NEMA-compliant voltage unbalance trip settings, it offers robust and adaptable performance across various three-phase applications. The 5-year unconditional warranty underscores its reliability, making it a dependable component for critical industrial infrastructure.

Dpdt 120V Universal 3-Ph

DOWNLOADS:

22lm

Specifications

Reset TypeManual Reset
Operating Voltage95-120 VAC
Power Consumption6W at 120V
Auto RangesNo
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay (Voltage/Unbalance Faults)1-30 sec., adjustable
Trip Delay (Single-Phasing Faults)1 sec., fixed
Trip Delay (Unbalance > 15%)1 sec., fixed
Restart Delay1-500 sec., adjustable
Manual Reset Input5V open circuit/500µA short circuit
Manual Reset RequirementExternal N.O. momentary pushbutton required
Output Contacts2X SPDT 10A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Terminal Torque (Power and Relay)9 in lbs max
Terminal Torque (Manual Reset)5.3 in lbs max
Wire Type (Power and Relay)12-22 AWG
Wire Type (Manual Reset)12-30 AWG
EnclosureNoryl plastic
MountingSurface Mount
Additional Options/SG = Silver with Gold Flash Contacts
System CompatibilityWye or Delta systems
Neutral ConnectionNot required
Dimension Tolerance± 0.06 in
Mounting Hole Diameter0.25 in
Warranty5-year Unconditional Warranty

FAQs

How is the 22-LM 3-Phase Monitor reset after a fault condition?
The 22-LM features a Manual Reset type. It requires an external N.O. momentary pushbutton for system re-engagement following a trip event.
What is the operating voltage range for the 22-LM monitor?
The 22-LM 3-Phase Monitor operates within a 95-120 VAC range, suitable for specific industrial power configurations.
Can the trip and restart delays be adjusted on the 22-LM unit?
Yes, the 22-LM offers adjustable delays. The Trip Delay for voltage and unbalance faults can be set from 1-30 seconds, and the Restart Delay is adjustable from 1-500 seconds.