Model 21-H 3-Phase Monitor (Auto Reset, 475-600 VAC)

21H

The Model 21-H 3-Phase Monitor ensures operational continuity in industrial environments. This auto-reset device provides comprehensive protection for 475-600 VAC systems. It actively monitors for critical conditions including phase loss, phase reversal, over/under voltage, and voltage unbalance, safeguarding connected equipment. Adjustable trip delay times, ranging from 1 to 30 seconds, allow for precise system-specific response tuning, preventing nuisance trips while ensuring timely intervention. A configurable restart delay, from 1 to 500 seconds, further enhances system stability and controlled recovery after fault conditions. Its robust SPDT 10A output contacts at 240VAC resistive integrate seamlessly into diverse control circuits. The unit's compact design and UL recognition confirm its suitability for demanding applications, contributing to reliable power system management and reduced downtime.

Universal 3Ph Monitor

DOWNLOADS:

21h

Specifications

Model TypeAuto Reset
Operating Voltage475-600 VAC
Power Consumption4.5W at 600V
Auto RangesNo
Monitored ConditionsPhase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay Time (Over, Under, & Unbalanced)1-30 sec., adjustable
Trip Delay Time (Single-Phasing Faults Unbalance > 15%)1 sec., fixed
Trip Delay Time (Reverse Phase)1 sec., fixed
Restart Delay1-500 sec., adjustable
Manual Reset Input5V open circuit/500µA short circuit
Output ContactsSPDT 10A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialNoryl plastic
Mounting8-Pin Socket (**sold separately)
Recommended Socket51x120
Additional Options/SG = Silver with Gold Flash Contacts
Agency ApprovalUL Recognized (U.S. and Canada) (For use in a Pollution Degree 2 Environment)
Neutral ConnectionNot required
System CompatibilityWye or Delta systems
Recommended Fuse1A 600VAC
Warranty5-year Unconditional Warranty

FAQs

What operating voltage range does the Model 21-H 3-Phase Monitor support?
The Model 21-H supports an operating voltage range of 475-600 VAC.
What specific electrical conditions does the Model 21-H monitor?
It monitors for phase loss, phase reversal, over/under voltage, and voltage unbalance.
Are the trip and restart delay times adjustable on the Model 21-H?
Yes, the trip delay time is adjustable from 1-30 seconds, and the restart delay is adjustable from 1-500 seconds.