15-240

15-240

The MODEL 15 Reverse Phase Correction Relay provides essential protection for industrial systems. Operating at 240VAC with a 50-60Hz frequency range, this device ensures consistent phase monitoring. Its rapid .05-second response and reset times minimize system downtime during phase anomalies, contributing to operational continuity. Robust SPDT 10A output contacts at 240VAC resistive and 3P3T 4A at 480VAC resistive contacts manage diverse load requirements effectively. Transient protection up to 2500V for 10ms safeguards connected equipment from voltage spikes. With an operating temperature range of -20° to +140° F and 0-97% humidity tolerance, the relay maintains performance in demanding industrial environments. The automatic reset function further enhances system reliability. Constructed with a NORYL case material, it offers durability. This unit provides dependable, precise phase correction for critical applications, supported by a 10 million mechanical operation life.

The Time Mark Model 15 was designed to protect your valuable equipment
from the damaging effects of phase reversal by sensing and automatically
correcting for phase reversal. Under normal power conditions, incoming
A B C voltage is passed straight through the device to the A B C output
terminals (4 amps @ 480 VAC resistive max). If the unit detects an
incoming reverse phase condition (C B A), it will light the reverse
phase LED and internally switch 2 of the phases and then pass the
corrected phasing out to output terminals A B C. If your load is higher
than 4 amps @ 480VAC resistive, the Model 15 provides an auxiliary
output relay to put in the control circuit of a remote reversing
contactor. If phasing is correct, the relay will remain in the static
condition (N.C contact will remain closed and N.O. will remain open). If
the Model 15 detects a reverse phase input, the auxiliary output relay
will energize and the relay contacts will switch (N.C contact will open
and N.O. will close).

Specifications

Nominal voltage (phase to phase)240VAC
Operating range± 10%
Frequency50 to 60Hz
Power consumption2W per phase
Transient protection2500V for 10ms
Repeat accuracy± 0.1% (fixed conditions)
Response time.05 seconds
Reset time.05 seconds
Reset typeAutomatic
Dead BandApproximately 2%
Output contacts (AUX)SPDT 10A at 240VAC resistive
Output contacts (3 Phase)3P3T 4A at 480VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 at rated load
Operating temperature-20° to +140° F
Humidity tolerance0 - 97% w/o condensation
Case materialNORYL
MountingSurface Mount
WarrantyUnconditional 5-Year Warranty

FAQs

What are the primary voltage and frequency specifications for the MODEL 15 Reverse Phase Correction Relay?
The relay operates at a nominal voltage of 240VAC with an operating range of ±10%. It is compatible with frequencies from 50 to 60Hz.
What are the output contact capabilities and expected lifespan of this relay?
It features SPDT 10A at 240VAC resistive auxiliary contacts and 3P3T 4A at 480VAC resistive 3-phase contacts. Expected mechanical relay life is 10 million operations, with 100,000 electrical operations at rated load.
Can the MODEL 15 Reverse Phase Correction Relay withstand harsh environmental conditions and electrical transients?
Yes, it tolerates operating temperatures from -20° to +140° F and 0-97% humidity without condensation. It also provides transient protection of 2500V for 10ms and is housed in a NORYL case.